Question 78: What inputs or trips are typically included in FCC flue gas expanders and CO (carbon monoxide) boilers' safety interlock systems? Are there any governing standards [(e.g., API and NFPA (National Fire Protection Association)] that apply?

I would like to address this question as two different parts, beginning with the flue gas expanders. BP has three flue gas expanders in its system. These expanders are all set up with slightly different configurations. We have one FCCU flue gas expander that is directly coupled to the main air blower.

Question 77: For our emergency interlock system, we employ two-out-of-three voting systems for slide valve differential pressure transmitters. We use dedicated transmitter taps for each transmitter, but we get inconsistent readings. What can we do, regarding design and maintenance, to ensure that these transmitters read more consistently? What should we do if we are unable to achieve consistent readings?

To obtain a more consistent reading, plant personnel should examine three phases: the transmitter, its physical location, and its instrument gas system. As for the transmitter, the technician should analyze it to ensure that it is within the accuracy specified by the manufacturer.

Question 76: The check valve on the air blower discharge line is designed to protect the blower from hot catalyst that backs into it when the blower fails. What type of valve is used in this service, where is it located, and what is done to ensure that it closes properly?

UOP specifies two special check valves in the blower discharge line. The first special check valve is installed a minimum distance from the blower discharge downstream in the snort (or anti-surge) valve in a horizontal pipe run.

Question 73: What is your experience with coke bed instability?

We have seen coke beds collapse during the beginning stages of the quench water addition. We have had operational problems because we were not able to get the quench water into the coke bed. We even tried alternating back and forth between the stripping steam and the quench water, but we were not able to penetrate the coke bed with the quench water.